Type: Bug
-
Status: Done (View Workflow)
-
Priority: Normal
-
Resolution: Done
-
Component/s: ics_enuActor
-
Story Points:2
-
Sprint:SM1PD-2020 C, SM1PD-2020 D, SM1PD-2020 G, SM1PD-2020 G2, SM1PD-2020 H, SM1PD-2020 J, SM1PD-2021 A 3, SM1PD-2021 A 4, SM1PD-2021 A 5, SM1PD-2021 A 6, SM1PD-2021 A 11
03:53:07.430948 spsait w text="enu_sm1 shutters failed: FysomError('event init inappropriate in current state FAILED',) in fn() at /software/conda/lib/python3.6/site-packages/fysom/_init_.py:272"
Don't know why they failed
Basically biasha board is stuck in a peculiar state where it doesn't answer correctly.
alefur@shell-ics:~$ oneCmd.py enu_sm1 biasha raw=status 2020-08-13T16:00:44.454 sent enu_sm1 biasha raw=status (from alefur_shell_ics) 2020-08-13T16:00:44.478 enu_sm1 : text="returned: 30" alefur@shell-ics:~$ oneCmd.py enu_sm1 biasha raw=statword 2020-08-13T16:01:01.772 sent enu_sm1 biasha raw=statword (from alefur_shell_ics) 2020-08-13T16:01:01.792 enu_sm1 : text="returned: n"
The only fix is to power cycle the board
- relates to
-
INSTRM-1239 Expose function operates blue shutter when when red is selected
- Won't Fix
-
INSTRM-1226 trigger an alert whenever biashaFSM[1]=="FAILED"
- Done
-
INSTRM-1232 add single enuActor top level command to fix biasha board issue.
- Done