The gatevalve open command from INSTRM-406 checks cryostat and roughing line pressures before opening. This is sufficient to be safe, but we should also check both turbo and roughing pump status just to be complete.
- relates to
-
INSTRM-406 Add safety logic to gatevalve control.
-
- Done
-
-
INSTRM-570 Add python-level interlock interrupt handler.
-
- Won't Fix
-
Merged at 92c3a98, tagged 1.7.12
Only checking pump speeds, but I think that is enough.
To open the gate valve underVacuum, both pumps must be running at the slow-to-reach full speed, which may annoy some.